Generator: Existing Solar & Storage

Use this article when a generator is installed at a home that already has solar, a battery, or both, or when it is installed together with a new Generac PWRcell 2 system. Confirm the site matches a row below before you install. Configurations not listed are not approved.

Before you install

  • Existing solar and batteries must stay on the utility side of the generator Automatic Transfer Switch (ATS).

  • When the home has an existing battery with a Microgrid Interconnection Device (MID), install the ATS after (downstream of) the battery's backup equipment, such as the Tesla Backup Gateway.

  • Include a clear photo of the existing battery's label showing the model number in the install package.

INSTALLER ALERT: Solar or a battery on the generator side of the ATS can send power back into the generator. EPCs should be aware of this limitation and refrain from utilizing this configuration.

Approved configurations

#

Existing equipment

Policy Status

Battery charges from generator?

Separate ATS required?

What to know

1

None

Approved

N/A

Yes

Standard generator install.

2

Solar only, any inverter

Approved when Conditions are Met

N/A

Yes

The generator backs up the home. Solar does not run during an outage.

3

Enphase IQ Battery 5P with 3G Controller

Approved when Conditions are Met

Yes

No. The Enphase system controls the transfer.

Works with generators on the Generator AVL if appropriately sized.

4

Enphase IQ Battery 10T with IQ System Controller 2

Approved when Conditions are Met

No

Yes

Install the ATS after the IQ System Controller 2.

5

Tesla Powerwall 3

Approved when Conditions are Met

No

Yes

Install the ATS after the Tesla MID.

6

SolarEdge Home Battery

Approved when Conditions are Met

No

Yes

Install the ATS after the SolarEdge Backup Interface.

7

FranklinWH

Approved when Conditions are Met

No

Yes

Install the ATS after the FranklinWH aGate.

8

Generac PWRcell 2, with or without PWRmicro solar

Approved

Yes

No

—

9

Any battery not listed above

Contact support before installing

—

—

—

—

Battery in rows 4 to 7 with no MID installed

Not Approved. Please do not install.

—

—

—

—

Solar or battery on the load side of the ATS

Not Approved. Please do not install.

—

—

—

For rows 4 to 7, the battery will not charge from the generator during an outage. Make sure the customer understands this at the point of sale. See the customer FAQs below.

FAQ

#

Question

Answer

1

Will my battery charge from the generator during an outage?

Yes with Generac PWRcell 2 or Enphase IQ Battery 5P. With other batteries, the battery and generator back up the home separately, and the generator will not recharge the battery.

2

Will my solar work during an outage?

Homes with solar and no battery rely on the generator during an outage.

3

Can I add a battery or solar later?

Yes. Speak with your installer regarding your options.

Did this answer your question?