Geothermal: Install Package Submission

Every residential geothermal lease program project must include the following four design documents. Submit all items prior to installation for project approval.

Permit Submission

Permits must be approved before the Loop Field milestone can be completed.

  • Permit document

  • Submitted Date

  • Approved Date

1. Manual J Load Calculation

Whole-house heating and cooling load calculation per ACCA Manual J, room-by-room.

  • Produced in ACCA-approved software (Wrightsoft, Elite RHVAC, or CoolCalc)

  • Block load and room-by-room loads included

  • Design conditions match project ZIP code (ACCA Table 1A)

  • Building inputs documented: orientation, insulation, windows, infiltration

2. Manual S Equipment Selection

Heat pump selection report demonstrating capacity match to Manual J loads at design conditions.

  • Selected heat pump model and AHRI certificate referenced

  • Total and sensible cooling capacity at design EWT vs. Manual J cooling load

  • Heating capacity at design EWT vs. Manual J heating load

  • Cooling oversizing within ACCA limits (≀115% total, humid climates per Manual S)

  • Auxiliary / backup heat sized and documented (required for Northeast projects)

3. Manual D Duct Design

Duct system design or evaluation of existing ductwork.

  • New construction or full replacement: full Manual D design submitted

  • Existing ducts: static pressure test and CFM verification documented

  • Airflow (CFM) per room aligns with Manual J room loads

4. Ground Loop Design Report

Loop sizing and configuration from an accepted geothermal design tool.

  • Produced in an accepted tool (see list below)

  • Loop type, total bore footage, borehole count, and depth specified

  • Design EWT/LWT, flow rate, and antifreeze solution documented

  • Ground thermal conductivity value used and source cited

  • Grout thermal conductivity and pipe specification (HDPE 3608 / 4710 / PEX-A) listed

  • Rule-of-thumb sizing (e.g., feet per ton) is NOT acceptable

Required Photos

Requirement

Description

Equipment Data Plate

Photo must show manufacturer's data plate with serial number, model number, and capacity rating clearly visible

Mechanical Room Wide Shot

Photo must show the complete heat pump unit and surrounding installation area, including connections, clearances, and piping

Flow Center

Photo must show flow center / circulator installation with connections to loop field and indoor unit

Loop Field Photo

Photo must show loop field installation, ideally before backfill. For Loop Field milestone submissions, this is required before backfill.

Electrical Disconnect

Photo must show electrical disconnect for the geothermal system, properly installed and accessible

Thermostat

Photo must show thermostat installed and configured for geothermal system operation